Readme
Power calculation from difference temperature
Formula: Power = (TSupply - TReturn) Water flow 1.0 * 4.18/3.6
Heating coefficient for water 20 - 100 °C = 4.18 (kJ/kg *K)
Density for water = 1.0 kg/l
Scale factor from m3/h to l/s =1/3.6
Comment on this Package
Watchers
1
Stars
3
2,137 views
• 111 downloads
Package Details
Author